Product Description
The VLT101517562035 is one of the Danfoss top notch products. For derating the VLT101517562035 for the low air pressure you should decrease the cooling capability of air at low air pressure. If you are using at an altitude above 6600 feet please refer to the Danfoss. No de-rating is necessary for the altitude below 3281ft [1000 m]. However, for the altitude above 3281 ft, the maximum output or the ambient temperature should be decreased. You have to decrease the output by 1% per 328 ft or decrease the maximum ambient temperature by at least 1° per 200 meter or 656 ft. The VLT101517562035 has four programmable digital inputs with the terminal number 18, 19, 27, and 29. It has a maximum 28 VDC voltage on input and the input resistance is approximate 4 k.
The VLT101517562035 must have minimum 0.05 mm2/30 AWG cross-section to control terminals. Below are the other features of analog inputs:
- Voltage level 0–10 V
- Input resistance, Ri approx. 10 kΩ
- Input resistance, Ri <500Ω
- Max. current 29 mA
- Max. voltage 20 V
- Current level 0/4 to 20 mA (scalable)
The VLT101517562035 has a total number of 2 analog inputs with terminal numbers 53 and 54. And, following are the features of the analog output.
- Current range at analog output 0/4–20 mA
- Max. load to common at analog output 500 Ω
- Resolution on analog output 10 bit
- Max. voltage at analog output 17 V
- Accuracy on analog output Max. error: 0.4% of full scale
The terminals of the VLT101517562035 can also be programmed as digital outputs which is great!