In-Stock, Ships Fast
Part Number:

KL3202-0000

Manufacturer: Beckhoff
Series: KL Analog Input Series

Current response time:

3 Minutes

6 Seconds

  • Rated 4.4 (14 total ratings)
  • Straightforward Pricing: No Rush Fees, No Credit Card Fees
Free Ground Shipping
Worldwide Delivery
Repair Options Available

The Beckhoff KL3202-0000 bus terminal supports Pt100 and Ni sensors. It features 500 V electrical isolation and a 60 mA typical K-bus power consumption.

In-Stock, Ships Fast
Part Number:

KL3202-0000

Manufacturer: Beckhoff
Series: KL Analog Input Series

Current response time:

5 Minutes

53 Seconds

  • Rated 4.4 (14 total ratings)
  • Straightforward Pricing: No Rush Fees, No Credit Card Fees
Free Ground Shipping
Worldwide Delivery
Repair Options Available

The Beckhoff KL3202-0000 bus terminal supports Pt100 and Ni sensors. It features 500 V electrical isolation and a 60 mA typical K-bus power consumption.

Preparing your secure checkout page...

Warranty
1-year-warranty Wake Industrial Warranty
Shipping
DHL Logo FedEx Logo
UPS Logo Freight Logo
DHL Logo FedEx Logo UPS Logo Freight Logo
Payment
Visa Logo AmEx Logo
Mastercard Logo Wire transfer Logo
Visa Logo AmEx Logo Mastercard Logo Wire transfer Logo
To Speak to a sales representative for pricing and lead time:

Product Description

The KL3202-0000 bus terminal is a temperature-measuring device developed for precise control and monitoring applications available from Beckhoff. The terminal is compatible with a wide range of resistance temperature detectors (RTDs), including Pt100, Pt200, Pt500, Pt1000, Ni100, Ni120, and Ni1000. Because of this, the terminal is ideal for use in industrial automation applications that require temperature measurement.

Two terminal ports on the KL3202-0000 bus terminal get power from the K-bus. There is no difference between two-wire and three-wire links. Many kinds of sensors can be used because the end is flexible. The Pt sensors on the product can record temperatures from -200°C to +850°C. Using Ni sensors, the terminal can record temperatures between -60°C and +250°C. The readout is accurate to within ±1°C, with a precision of 0.1°C for each digit. The time required for the conversion is approximately 250 ms, and the current typically measured is 0.5 mA. Resistance to electromagnetic fields and emissions and shaking and shock are two areas where this terminal excels. The K-bus and signal voltage are well protected by the 500 V electrical separation at the KL3202-0000 bus end.

There are no power connections on the terminal, and it only draws 60 mA from the K-bus. The terminal features control and status bits, and it can accept two 16-bit data inputs. It simplifies configuration via the Bus Coupler or driver because it can detect whether a circuit is open and does not require addressing. The operating temperature range for the KL3202-0000 bus terminal is -25°C to +60°C, and the storage temperature range is -40°C to +85°C. The terminal has an IP20 certification for protection and weighs around 70 grams. The product is available for global shipment by Wake Industrial and comes with a year replacement warranty.

KL3202-0000 Technical Specifications

Input Type: Temperature, RTD (Pt100)
Bit Width In The Process Image: input: 2 x 16 bit data (2 x 8 bit control/status optional)
Weight: approx. 70 g
Operating/storage Temperature: -25…+60°C/-40…+85°C
Vibration/shock Resistance: conforms to EN 60068-2-6/EN 60068-2-27
Emc Immunity/emission: conforms to EN 61000-6-2/EN 61000-6-4
Protection Rating/installation Position: IP20/variable
Resolution: 16 bit
Measuring Range: -200…+850°C (Pt sensors); -60…+250°C (Ni sensors)
Connection Method: 2- or 3-wire (default: 3-wire)
Conversion Time: ~ 250 ms
Measuring Current: typ. 0.5 mA
Measurement Error/uncertainty: < ±1°C
Current Consumption Power Contacts: – (no power contacts)
Current Consumption K-bus: typ. 60 mA

Frequently Asked Questions about KL3202-0000


Q: Does the KL3202-0000 bus terminal have open-circuit recognition?

A: Yes, the KL3202-0000 features open-circuit recognition. This function enhances safety by detecting sensor disconnection during operation.

Q: How does the KL3202-0000 bus terminal achieve 500 V isolation?

A: The KL3202-0000 uses electrical isolation to separate the K-bus from signal voltage. This protects the system from potential voltage surges.

Q: How does KL3202-0000 bus terminal ensure ±1°C accuracy?

A: The KL3202-0000 ensures ±1°C accuracy through precise sensor calibration. This minimizes errors in temperature measurements across wide ranges.

Q: Do Pt100 and Ni sensors work with KL3202-0000 terminal?

A: Yes, the KL3202-0000 supports Pt100 and Ni sensors. It allows compatibility with different sensor types for varied applications.

Q: Why does the KL3202-0000 bus terminal conform to EMC standards?

A: The KL3202-0000 conforms to EMC standards to minimize electromagnetic interference. This ensures reliable operation in electromagnetic environments.

Internal Product Review

  • ‘‘The Beckhoff KL3202-0000 bus terminal offers high precision with a resolution of 0.1°C per digit and a conversion time of 250 ms. The device provides flexibility with 2- or 3-wire sensor connections. It includes open-circuit recognition and complies with EMC and vibration standards, ensuring reliability in demanding applications.’’

Motion Industries logo
3M logo
IBM logo
Gexpro Logo
Caterpillar logo
NASA logo
Ford logo
Vallen logo