The EL1008-0000 EtherCAT Terminal features 8 inputs, a typical input current of 3 mA, and operates at a nominal voltage of 24 V DC with a -15% to +20% variation. Part of the EL EtherCAT Terminal Series from Beckhoff, it is designed with an operating temperature range of -25…+60°C and EMC Immunity/emission compliant with EN 61000-6-2 standards.

Part Number:

EL1008-0000

Manufacturer: Beckhoff
Series: EL EtherCAT Terminal Series
  • Rated 4.5 (38 total ratings)
  • Straightforward Pricing: No Rush Fees, No Credit Card Fees
    In-Stock, Ships in 3 Days
  • Call for Expedited Shipping and Product Condition Options
Free Ground Shipping
Worldwide Delivery
Repair Options Available

The EL1008-0000 EtherCAT Terminal features 8 inputs, a typical input current of 3 mA, and operates at a nominal voltage of 24 V DC with a -15% to +20% variation. Part of the EL EtherCAT Terminal Series from Beckhoff, it is designed with an operating temperature range of -25…+60°C and EMC Immunity/emission compliant with EN 61000-6-2 standards.

Preparing your secure checkout page...

Warranty
1-year-warranty Wake Industrial Warranty
Shipping
DHL Logo FedEx Logo
UPS Logo Freight Logo
DHL Logo FedEx Logo UPS Logo Freight Logo
Payment
Visa Logo AmEx Logo
Mastercard Logo Wire transfer Logo
Visa Logo AmEx Logo Mastercard Logo Wire transfer Logo
To Speak to a sales representative for pricing and lead time:

Product Description

The EL1008-0000 is a Beckhoff EtherCAT terminal designed for connecting up to eight digital inputs in automation systems. This compact device facilitates the integration of various sensors and switches, allowing for efficient data acquisition and control in industrial applications. It features eight digital inputs, allowing for versatile data collection and monitoring in applications that require the integration of various input devices. The terminal features a 24 V DC nominal voltage and offers a -15% to +20% tolerance. It has a “0” signal voltage range of -3 to +5 V and a “1” signal voltage range of 11 to 30 V. This voltage capacity offers compatibility with a wide variety of digital input devices.

The terminal typically requires an input current of 3 mA, ensuring a low current consumption that contributes to the terminal's compatibility with various input devices. It comes with an input filter with a typical response time of 3.0 ms that helps to stabilize signal processing by reducing the effects of noise. The terminal typically consumes 2 mA of current from the power contacts, ensuring efficient power management in automation systems. For the E-bus, it has a typical current consumption of 90 mA. The terminal offers a 500 V isolation between the E-bus and field potential, safeguarding against spikes in voltage.

The EL1008-0000 carries multiple approvals and markings, including CE, UL, ATEX, IECEx, DNV GL, and cFMus. These certifications ensure compliance with international safety and performance regulations. It is optimized for use in harsh environments with a robust but slim design that weighs 55 g and measures 12 mm x 100 mm x 68 mm. This small form factor delivers seamless integration with minimal installation requirements.

EL1008-0000 Technical Specifications

Number Of Inputs: 8
Special Features: standard input terminal for bouncing signals (filter 3 ms)
Weight: approx. 55 g
Operating/storage Temperature: -25…+60°C/-40…+85°C
Vibration/shock Resistance: EN 60068-2-6/EN 60068-2-27
Emc Immunity/emission: EN 61000-6-2/EN 61000-6-4
Protection Rating/installation Position: IP20/see documentation
Nominal Voltage: 24 V DC (-15%/+20%)
0 Signal Voltage: -3…+5 V (EN 61131-2, type 3)
1 Signal Voltage: 11…30 V (EN 61131-2, type 3)
Input Current: typ. 3 mA (EN 61131-2, type 3)
Input Filter: typ. 3.0 ms
Distributed Clocks: No
Current Consumption Power Contacts: typ. 2 mA + load
Current Consumption E-bus: typ. 90 mA

Frequently Asked Questions about EL1008-0000


Q: What is the nominal voltage of the EL1008-0000?

A: The EL1008-0000 operates at a nominal voltage of 24 V DC, with a tolerance range of -15% to +20%. This flexibility ensures compatibility with various power supply setups.

Q: How many digital inputs does the EL1008-0000 support?

A: The EL1008-0000 supports a total of eight digital inputs. This allows for the connection of multiple sensors and switches, enhancing the versatility of automation systems.

Q: What is the input current for the EL1008-0000?

A: The EL1008-0000 typically requires an input current of 3 mA, ensuring energy efficiency of the device in various applications.

Q: What is the electrical isolation rating of the EL1008-0000?

A: The EL1008-0000 provides electrical isolation of 500 V between the E-bus and field potential. This isolation enhances safety by protecting internal circuits from potential voltage spikes and noise.

Q: What type of mounting does the EL1008-0000 support?

A: The EL1008-0000 is designed for installation on a 35 mm DIN rail, conforming to EN 60715. It allows for side-by-side mounting through a double slot and key connection, promoting efficient space utilization.

Internal Product Review