The Beckhoff BK5200 unit is part of the BK EtherCAT Bus Coupler Series and features a bus interface with one open pluggable 5-pin connector. It handles digital signals with 512 inputs/outputs, and analog signals with 256 inputs/outputs. The device's EMC immunity conforms to EN 61000-6-2/EN 61000-6-4 standards.

Part Number:

BK5200

Manufacturer: Beckhoff
Series: BK EtherCAT Bus Coupler Series
  • Rated 4.6 (17 total ratings)
  • Straightforward Pricing: No Rush Fees, No Credit Card Fees
  • Call for Expedited Shipping and Product Condition Options
Free Ground Shipping
Worldwide Delivery
Repair Options Available

The Beckhoff BK5200 unit is part of the BK EtherCAT Bus Coupler Series and features a bus interface with one open pluggable 5-pin connector. It handles digital signals with 512 inputs/outputs, and analog signals with 256 inputs/outputs. The device's EMC immunity conforms to EN 61000-6-2/EN 61000-6-4 standards.

Preparing your secure checkout page...

Warranty
1-year-warranty Wake Industrial Warranty
Shipping
DHL Logo FedEx Logo
UPS Logo Freight Logo
DHL Logo FedEx Logo UPS Logo Freight Logo
Payment
Visa Logo AmEx Logo
Mastercard Logo Wire transfer Logo
Visa Logo AmEx Logo Mastercard Logo Wire transfer Logo
To Speak to a sales representative for pricing and lead time:

Product Description

This second-generation Beckhoff EtherCAT Bus Coupler BK5200 from the BK EtherCAT Bus Coupler Series is designed to provide the optimal connection between EtherCAT communication and modular terminal input/output systems.

This bus coupler has 64 bus terminal connections, making it possible to expand the system to control and/or manage digital and/or analog signals within industrial applications. The BK5200 delivers a high data transfer rate for both digital and analog signals owing to its 512-byte input and output size for byte, digital, and data signals. It may be utilized for a wide range of automation applications because it contains 512 digital inputs and outputs and 256 analog inputs and outputs. With the use of KS2000 software or directly through the controller, these terminals can be readily modified to satisfy specific operating requirements. Data transfer rates are configured by a Dip switch that is easy to use and useful for controlling the data transfer speeds. The bus interface has a 5-pin open pluggable connector, supplied with the product, for simple and secure connection to networks. The data transfer medium used is screened twisted copper wire with a power supply; a 5-pin connector is recommended for safe and continuous data transfer. The power supply of BK5200 is 24 V DC, the tolerance is -15+/+20% and the power can be provided through a bus cable of 11-25 V.

It has a start current of about 2.5 times the continuous current and a recommended fuse not greater than 10A. The input current requirement is set to 70 mA with an additional ¼ of the total K-bus current but not more than 500 mA. Power at the K-bus is also evident through the provision of a 1750 mA current supply through the coupler. The device has several working modes such as; bit strobe, polling, cyclic, COS, and others that make it suitable to operate in different dynamic conditions of a system. Wake Industrial provides a one-year warranty on this product.

BK5200 Technical Specifications

Number Of Bus Terminals: 64
Input Current: 70 mA + (total K-bus current)/4, 500 mA max.
Starting Current: approx. 2.5 x continuous current
Recommended Fuse: ≤ 10 A
Current Supply K-bus: 1750 mA
Power Contacts: max. 24 V DC/max. 10 A
Operating Modes: bit strobe, polling, cyclic, change of state (COS)
Fieldbus: 512 byte input and 512 byte output
Digital Peripheral Signals: 512 inputs/outputs
Analog Peripheral Signals: 256 inputs/outputs
Configuration Possibility: via KS2000 or the controller
Data Transfer Rates: via Dip switch
Bus Interface: 1 x open pluggable connector, 5-pin, included
Data Transfer Medium: screened, twisted copper wire with power supply, 5-pin
Power Supply: 24 V DC (-15%/+20%), through bus cable 11…25 V

Frequently Asked Questions about BK5200


Q: How many terminal connections does the BK5200 support and what types of signals can it manage?

A: The BK5200 supports 64 bus terminal connections and can manage both digital and analog signals, allowing it to handle a diverse range of automation applications.

Q: What is the data capacity for inputs and outputs on the BK5200?

A: It offers an input and output size of 512 bytes, suitable for efficient data transfer of both digital and analog signals.

Q: Can the data transfer rates of the BK5200 be adjusted?

A: Yes, data transfer rates on the BK5200 can be configured using a Dip switch, enabling adjustments to suit different operational needs within industrial applications.

Q: What type of connectors does the BK5200 use for its bus interface and power supply?

A: The BK5200 uses a 5-pin open pluggable connector for its bus interface and recommends a 5-pin connector for the power supply to ensure secure and reliable connections.

Q: What power specifications does the BK5200 have, and what are its operational modes?

A: The BK5200 requires a 24 V DC power supply with a tolerance of -15%/+20% and can operate in several modes, including bit strobe, polling, cyclic, and COS, to adapt to various dynamic conditions in an industrial setting.