X20AT6402
Wake Industrial LLC is not an authorized distributor of this product.
- Straightforward Pricing: No Rush Fees, No Credit Card Fees
-
In-Stock, Ships 1-2 Days
The X20AT6402 module features 6 thermocouple inputs compatible with types J, K, N, S, B, R, with a resolution of 0.1 degrees C and a 16-bit digital converter resolution. Part of the X20 Series manufactured by B & R Automation, it offers configurable filter times between 1 ms and 66.7 ms.
To contact sales for pricing and lead time:
Payment Methods




Shipping Methods




Our Credentials




Product Description:
The X20AT6402 module by B&R Automation is an advanced thermocouple input module designed to accommodate six different types of thermocouples: J, K, N, S, B, and R. This variety allows it to cover a wide range of temperatures in different industries and is highly effective in capturing accurate thermal data.
With a resolution of 0. 1 degrees C and a 16-bit digital converter, the module provides an efficient, precise temperature control to meet the needs of critical industrial processes. The X20AT6402 has many features and one of them is configurability. It has filter times that are adjustable from 1ms to 66. 7 ms, enabling users to adjust the module's sensitivity to its surroundings and increase the accuracy of the readings. Conversion times are also considered to be efficient, and they take 80. 4 ms were needed for a single channel with a 50 Hz filter. For multiple channels, the time is ( (n + 1) times 40. 2 ) ms per channel at the same filter frequency for data processing to be done effectively even when several sensors are active. The module supports a wide range of temperature measurements: Platinum: Type J from -210 to 1200 degrees C, Type K from -270 to 1372 degrees C, and Type N from -270 to 1300 degrees C. Type S thermocouples have a temperature range of -50 to 1768 degrees C, Type B from 0 to 1820 degrees C, and Type R from -50 to 1664 degrees C. This versatility ensures that temperature sensing can be done properly in diverse industries.
The specifications allow the X20AT6402 to be used in several environments, including high-temperature furnaces and low-temperature environmental chambers. This module is designed to work efficiently within a terminal temperature range of -25 to 85 degrees C and meets the standard of EN 60584, which is the international standard for thermocouples. This makes the X20AT6402 a good option for industries that need reliable and accurate temperature monitoring systems. The product is available at Wake Industrial with a one-year warranty period.
Frequently Asked Questions about X20AT6402:
Q: Which thermocouple types are compatible with the B&R X20AT6402 module?
A: The X20AT6402 module is compatible with six thermocouple types: J, K, N, S, B, and R, covering a wide range of temperature measurements.
Q: How accurate is the X20AT6402 module's temperature measurement?
A: The X20AT6402 module provides high accuracy with a resolution of 0.1 degrees C, supported by a 16-bit digital converter, ensuring precise temperature control in industrial applications.
Q: What is the operating temperature range for the X20AT6402 module?
A: The X20AT6402 module operates within a terminal temperature range of -25 to 85 degrees C, making it suitable for various environmental conditions in industrial settings.
Q: How does the X20AT6402 module handle multiple channels?
A: The X20AT6402 module features efficient conversion times, processing a single channel in 80.4 ms with a 50 Hz filter, and multiple channels at ( (n + 1) times 40.2 ) ms per channel, ensuring timely data capture even with several active sensors.
Q: What standards does the X20AT6402 module meet?
A: The X20AT6402 module complies with the EN 60584 standard, which is the international standard for thermocouples, ensuring reliable and consistent temperature measurements.