The KM2004-0000 bus terminal features 32 outputs with a nominal voltage of 24 V DC, a short-circuit proof max output current of 0.5 A per channel, and reverse voltage protection. Part of the KM Bus Terminal Series by Beckhoff, it handles ohmic and inductive loads and meets EMC immunity standards EN 61000-6-2 and EN 61000-6-4.

Part Number:

KM2004-0000

Manufacturer: Beckhoff
Series: KM Bus Terminal Series
  • Rated 4.5 (23 total ratings)
  • Straightforward Pricing: No Rush Fees, No Credit Card Fees
    In-Stock, Ships 3-5 Days
  • Call for Expedited Shipping and Product Condition Options
Free Ground Shipping
Worldwide Delivery
Repair Options Available

The KM2004-0000 bus terminal features 32 outputs with a nominal voltage of 24 V DC, a short-circuit proof max output current of 0.5 A per channel, and reverse voltage protection. Part of the KM Bus Terminal Series by Beckhoff, it handles ohmic and inductive loads and meets EMC immunity standards EN 61000-6-2 and EN 61000-6-4.

Preparing your secure checkout page...

Warranty
1-year-warranty Wake Industrial Warranty
Shipping
DHL Logo FedEx Logo
UPS Logo Freight Logo
DHL Logo FedEx Logo UPS Logo Freight Logo
Payment
Visa Logo AmEx Logo
Mastercard Logo Wire transfer Logo
Visa Logo AmEx Logo Mastercard Logo Wire transfer Logo
To Speak to a sales representative for pricing and lead time:

Product Description

The Beckhoff Automation KM2004-0000 terminal module is made to make complicated automation jobs easier. The module can be used in situations where fine control over multiple output channels is needed, and it is designed to work with other systems without any problems. The module makes sure that operation and upkeep are reliable, with few extra parts needed.

The KM2004-0000 terminal module has 32 output channels that are split into 4 groups of 8. The terminal works with a nominal power of 24 V DC. Each channel can handle a maximum output current of 0.5 A and can't short-circuit because the short-circuit current stays below 2 A. The breaking energy of the product is less than 150 mJ per channel, and it protects against reverse voltage. The terminal can handle a lot of different types of loads, such as ohmic, magnetic, and lamp loads. The KM2004-0000 module uses 5 mA from the K-bus, with 500 V of electrical isolation between the K-bus and field potential. The terminal meets the standards for EMC protection and emissions set by EN 61000-6-2 and EN 61000-6-4, that are needed for industrial automation.

Following the EN 60068-2-6 and EN 60068-2-27 standards, the module can withstand shaking and shock. It can also work in temperatures ranging from 0 to +55°C and be stored at temperatures ranging from -25°C to +85°C. The module is placed on a 35 mm rail in line with EN 60715 standards. It is made to be easy to connect using plug connection technology. The protection level is IP20, and the weight ranges from 90 to 110 g, based on the type of connector. The sizes stay the same, at about 75 mm x 100 mm x 55 mm. We offer a one-year replacement warranty and ship our automation products all over the world.

KM2004-0000 Technical Specifications

Connection Technology: plug
Current Consumption K-bus: typ. 5 mA
Bit Width In The Process Image: 32 outputs
Weight: approx. 90 g with 1-pin connector, approx. 110 g with 3-pin connector
Operating/storage Temperature: 0…+55°C/-25…+85°C
Vibration/shock Resistance: conforms to EN 60068-2-6/EN 60068-2-27
Emc Immunity/emission: conforms to EN 61000-6-2/EN 61000-6-4
Number Of Outputs: 32 (4 x 8)
Nominal Voltage: 24 V DC (-15%/+20%)
Load Type: ohmic, inductive, lamp load
Max. Output Current: 0.5 A (short-circuit proof) per channel
Short-circuit Current: < 2 A
Breaking Energy: < 150 mJ/channel
Reverse Voltage Protection: yes
Current Consumption Power Contacts: none (no power contacts)

Frequently Asked Questions about KM2004-0000


Q: What voltage does the KM2004-0000 module require?

A: The KM2004-0000 operates at 24 V DC. It ensures compatibility with standard industrial power supplies.

Q: How many outputs does KM2004-0000 module have?

A: The KM2004-0000 features 32 outputs. This allows extensive control capabilities across multiple channels.

Q: Is the KM2004-0000 module short-circuit proof?

A: Yes, the KM2004-0000 module is short-circuit proof. Each channel can handle up to 0.5 A safely.

Q: What load types can KM2004-0000 handle?

A: The KM2004-0000 can manage ohmic, inductive, and lamp loads. This versatility supports a range of application needs.

Q: Does KM2004-0000 have reverse voltage protection?

A: Yes, the KM2004-0000 includes reverse voltage protection. This feature prevents damage from incorrect voltage connections.