Part Number:

KL3311-0100

Manufacturer: Beckhoff
Series: KL Analog Input Series
  • Rated 4.4 (7 total ratings)
  • Straightforward Pricing: No Rush Fees, No Credit Card Fees
  • Call for Expedited Shipping and Product Condition Options
Free Ground Shipping
Worldwide Delivery
Repair Options Available

The Beckhoff KL3311-0100, part of the KL Analog Input Series, features a connection method that is 2-wire and supports various thermocouple sensor types, including type K. It has a resolution of 0.1°C per digit and operates within a measuring range from -100 to +1370°C. Weighing approximately 70 grams, the device is electrically isolated and IP20 rated.

Part Number:

KL3311-0100

Manufacturer: Beckhoff
Series: KL Analog Input Series
  • Rated 4.4 (7 total ratings)
  • Straightforward Pricing: No Rush Fees, No Credit Card Fees
  • Call for Expedited Shipping and Product Condition Options
Free Ground Shipping
Worldwide Delivery
Repair Options Available

The Beckhoff KL3311-0100, part of the KL Analog Input Series, features a connection method that is 2-wire and supports various thermocouple sensor types, including type K. It has a resolution of 0.1°C per digit and operates within a measuring range from -100 to +1370°C. Weighing approximately 70 grams, the device is electrically isolated and IP20 rated.

Preparing your secure checkout page...

Warranty
1-year-warranty Wake Industrial Warranty
Shipping
DHL Logo FedEx Logo
UPS Logo Freight Logo
DHL Logo FedEx Logo UPS Logo Freight Logo
Payment
Visa Logo AmEx Logo
Mastercard Logo Wire transfer Logo
Visa Logo AmEx Logo Mastercard Logo Wire transfer Logo
To Speak to a sales representative for pricing and lead time:

Product Description

The Beckhoff KL3311-0100 is a small thermocouple terminal that is made to measure temperatures accurately. The thermocouple works with different kinds of thermocouple sensors, so it can be used in situations that need accuracy and dependability. The EL3311 works with the K-bus system, that makes connection and integration within industrial automation systems very easy.

The KL3311-0100 thermocouple terminal can work with J, K, L, B, E, N, R, S, T, and U sensor types, and type K is the usual setting. Type K thermocouples can be used to measure temperatures between -100°C and +1370°C. The terminal can also measure millivolts between ±30 mV and ±120 mV. The connection is made of two wires, and the conversion time is around 200 ms. The EL3311 has a wire failure indicator that makes it more reliable to use, and the terminal has a resolution of 0.1°C per digit and an error rate of less than ±0.5% when compared to the full-scale number. Between the K-bus and the signal power, there is electrical isolation of up to 500 V.

The KL3311-0100 has a weight of about 70 grams and can work in temperatures from 0°C to +55°C. It can be stored at temperatures from -25°C to +85°C. The unit meets the requirements of EN 60715 and can be mounted on a 35 mm DIN rail. IP20 protects the terminal and has a double slot and key connection that allows it to be placed next to each other. The terminal meets the standards for EMC protection and emissions (EN 61000-6-2 and EN 61000-6-4). It has approvals from CE, ATEX, UL, and IECEx. We guarantee that all our products will work properly, and we provide a replacement warranty in case of malfunction.

KL3311-0100 Technical Specifications

Number Of Inputs: 1
Current Consumption K-bus: typ. 65 mA
Bit Width In The Process Image: input: 1 x 16 bit data (1 x 8 bit control/status optional)
Special Features: electrically isolated
Weight: approx. 70 g
Operating/storage Temperature: 0…+55°C/-25…+85°C
Vibration/shock Resistance: conforms to EN 60068-2-6/EN 60068-2-27
Power Supply: via the K-bus
Thermocouple Sensor Types: types J, K, L, B, E, N, R, S, T, U (default setting type K), mV measurement
Measuring Range: type K; -100…+1370°C; mV measurement: ±30 mV…±120 mV
Connection Method: 2-wire
Conversion Time: ~ 200 ms
Wiring Fail Indication: yes
Resolution: 0.1°C per digit
Measurement Error/uncertainty: < ±0.5% (relative to full scale value)

Frequently Asked Questions about KL3311-0100


Q: Why does the Beckhoff KL3311-0100 support multiple thermocouple types?

A: The KL3311-0100 supports multiple thermocouple types to offer flexibility in different temperature measurement applications. This allows compatibility with various sensors.

Q: Does the Beckhoff KL3311-0100 provide electrical isolation?

A: Yes, the KL3311-0100 offers electrical isolation up to 500 V. This enhances safety by preventing electrical interference between signals.

Q: How does the Beckhoff KL3311-0100 indicate wiring failures?

A: The KL3311-0100 features a wiring failure indication to alert users of connection issues. This improves system reliability and reduces downtime.

Q: How fast is the conversion time on KL3311-0100?

A: The KL3311-0100 has a conversion time of approximately 200 ms. This ensures rapid processing of temperature measurements in real-time.

Q: Why does the Beckhoff KL3311-0100 feature 0.1°C resolution?

A: The 0.1°C resolution offers high precision in temperature readings. This enhances accuracy, especially in applications requiring fine measurement details.

Internal Product Review

  • ‘‘The Beckhoff KL3311-0100 thermocouple terminal is a reliable choice for temperature measurement across various thermocouple types. With a fast conversion time of 200 ms and ±0.5% accuracy, it ensures precise readings. Its compact design and compliance with multiple certifications make it suitable for demanding applications.’’

Motion Industries logo
3M logo
IBM logo
Gexpro Logo
Caterpillar logo
NASA logo
Ford logo
Vallen logo