Part Number:

EL1809

Manufacturer: Beckhoff
Series: EL EtherCAT Terminal Series
  • Rated 4.4 (37 total ratings)
  • Straightforward Pricing: No Rush Fees, No Credit Card Fees
    In-Stock, Ships 1-2 Days
  • Call for Expedited Shipping and Product Condition Options
Free Ground Shipping
Worldwide Delivery
Repair Options Available

The Beckhoff EL1809 digital input terminal features 16 input channels and a nominal voltage of 24 V DC. It is ideal for space-saving installations and provides electrical isolation up to 500 V.

Part Number:

EL1809

Manufacturer: Beckhoff
Series: EL EtherCAT Terminal Series
  • Rated 4.4 (37 total ratings)
  • Straightforward Pricing: No Rush Fees, No Credit Card Fees
    In-Stock, Ships 1-2 Days
  • Call for Expedited Shipping and Product Condition Options
Free Ground Shipping
Worldwide Delivery
Repair Options Available

The Beckhoff EL1809 digital input terminal features 16 input channels and a nominal voltage of 24 V DC. It is ideal for space-saving installations and provides electrical isolation up to 500 V.

Preparing your secure checkout page...

Warranty
1-year-warranty Wake Industrial Warranty
Shipping
DHL Logo FedEx Logo
UPS Logo Freight Logo
DHL Logo FedEx Logo UPS Logo Freight Logo
Payment
Visa Logo AmEx Logo
Mastercard Logo Wire transfer Logo
Visa Logo AmEx Logo Mastercard Logo Wire transfer Logo
To Speak to a sales representative for pricing and lead time:

Product Description

The EL1809 is an HD EtherCAT Terminal from Beckhoff that acquires binary control signals and transmits them to higher-level automation devices in an electrically isolated form. Designed with 16 input channels, this EtherCAT terminal is ideal for space-saving control cabinet installations. The terminal's single-conductor connection technique allows for multi-channel sensor integration with minimal wiring to make its use of space efficient.

The EL1809 operates on a nominal voltage of 24 V DC with a tolerance range of -15% to +20%. The terminal features an input filter with a typical response time of 3.0 ms that allows the terminal to handle slow 24 V DC edge signals effectively. The terminal supports a signal voltage range from -3 to +5 V for a "0" signal and 11 to 30 V for a "1" signal. The 16 input channels are represented with a bit width of 16 in the process image. The electrical isolation is rated at 500 V to ensure protection between system components. The current consumption on the E-bus is typically 100 mA, and power contact consumption is approximately 4 mA plus load. For conductor connections, the EL1809 HD EtherCAT Terminal supports solid wires, stranded wires, and ferrules to offer flexible installation options. Solid wire conductors are connected using a direct plug-in technique, while stranded wires and ferrules require spring actuation with a screwdriver.

The EL1809 is designed to meet various international standards to hold certifications like CE, UL, and ATEX to make it a reliable choice in industrial automation. The rated cross-section for solid wire ranges from 0.08 to 1.5 mm^2, and for stranded wire, it ranges from 0.25 to 1.5 mm^2. The terminal's compact design, ease of installation, and robust electrical specifications make it highly suitable for diverse automation tasks.

EL1809 Technical Specifications

Number of Inputs: 16
Connection Technology: 1-wire
Rated Cross-Section: 0.14-0.75 mm^2
Certifications: CE, UL, ATEX
Nominal Voltage: 24 V DC (-15%/+20%)
Input Filter: Typ. 3.0 ms
Conductor Types: Solid wire, stranded wire, and ferrule
Current Consumption: Typ. 100 mA
Signal Voltage ("0"): -3 to +5 V
Signal Voltage ("1"): 11-30 V
Electrical Isolation: 500 V
Bit Width in Process: 16 inputs

Frequently Asked Questions about EL1809


Q: Why does EL1809 have an input filter?

A: The EL1809 has a 3.0 ms input filter to handle slow 24 V DC edges. It ensures stable signal acquisition.

Q: How does EL1809 achieve electrical isolation?

A: The EL1809 provides 500 V of electrical isolation between the input channels and higher-level automation devices. This protects connected components.

Q: What signal voltages does EL1809 handle?

A: The EL1809 processes a "0" signal between -3 and +5 V and a "1" signal between 11 and 30 V.

Q: What is the conductor connection method for EL1809?

A: For solid wires, the EL1809 uses a direct plug-in technique. Stranded wires and ferrules are connected via spring actuation using a screwdriver.

Q: How much current does EL1809 consume from the E-bus?

A: The EL1809 consumes approximately 100 mA from the E-bus. This ensures its functionality while maintaining low power consumption.